Welcome to Phil Indo Tech Naga Corporation

Products

Solace

Heavy Duty, 1-bolt, Fire Performance Cable Cleat

The Solace Heavy Duty, One Bolt, High Temperature Fire Rated Stainless Steel single cable cleat is a cast metallic cleat which has been designed, constructed, and tested in accordance with the International Standard ‘Cable Cleats for Electrical Installations’ (IEC 61914).

These Fire Rated cable cleats can be used with fire performance cables to ensure the safe retention and securing of single cables in the event of a wiring system being affected by fire. These fire resisting supports help to maintain the electrical system’s integrity for any critical circuits during an emergency situation to enable safe evacuation. The cable cleat is manufactured from Stainless Steel 316L making it suitable for both indoor and outdoor applications. Due to its unique twin arc internal patent pending design profile it exhibits excellent retention, limiting both the axial and lateral movement.

The Solace One Bolt High Temperature Stainless Steel cable cleat is available in twelve sizes suitable for cable diameters of 10mm up to 71mm. The cable cleat has an M10 clearance hole for securing it to a mounting surface.

Features

  • 316L Stainless Steel
  • Operating temperature -60°C to +250°C
  • Surpasses requirements of Fire testing BS5839 / BS8491 / EN50200 / BS8434 / AS-NZS 3013 (1,200°C) (Fire, shock & water)
  • 10 – 71mm cable range take in 12 sizes
  • Single bolt fixing design
  • Can be stacked
  • Excellent axial & lateral load retention
  • Corrosion resistant
Short Circuit Testing to IEC 61914 – Clause 9.5
Parallel Formation
One short circuit 600mm fixed cleat centres 100mm cable centres Two short circuit 600mm fixed cleat centres 100mm cable centres
0.1 sec 0.1 sec
100kA Peak 100kA Peak
47.6kA RMS 47.6kA RMS
BS 5839 ‘Fire detection and fire alarm systems for buildings. Code of practice
for design, installation, commissioning and maintenance of systems
in non-domestic premises’
States that “Methods of cable support should be non-combustible and such
that circuit integrity will not be reduced below that afforded by the cable used, and should withstand a similar temperature and duration to that of the cable,
while maintaining adequate support”
To adhere to this BSI standard fire rated Cable Cleats must be used to support
the cable in the event of a fire.

Reviews

There are no reviews yet.

Be the first to review “Solace”

Your email address will not be published.